MAGIC RAIN L.S.S., Inc.
Post Office Box 364, Hinckley, OH 44233
(Serving Cuyahoga, Medina, Lorain & Summit Cos.) Phone: 330-220-RAIN (7246) and 330-220-9246 email: sandra@magicrain.com
It's Springtime!
The PVB is the #1 Backflow Device Unit, currently, recommended by the Ohio EPA.
Additionally, at the bottom of this page, are PVB RELEASE INSTRUCTIONS for the added convenience of our Clients.
Pressure Vacuum Breaker
Description of the PVB Backflow Device
Backflow device configured with a spring-loaded float and an independent spring loaded check valve. Check valve that is designed to close with the aid of a spring when flow stops. It also has an air inlet valve that is designed to open when the internal pressure is one psi above atmospheric pressure so that no non-potable liquid may be siphoned back into the potable water system. Being spring -loaded it does not rely upon gravity, as does the atmospheric vacuum breaker. This assembly includes resilient seated shut-off valves and test cocks. The PVB must be installed at least twelve (12) inches above all downstream piping and outlets. The PVB may be used to protect against a pollutant or contaminant; however, it may only be used to protect against backsiphonage. It is not acceptable protection against backpressure.